Guide to Thermostatic Expansion Valves

Learn how thermostatic expansion valves work in HVAC systems.

Originally published on June 24, 2013

Understanding TXVs

Since the minimum efficiency regulation changed to 13 SEER in January 2006, most OEM systems now incorporate a thermostatic expansion valve (TXV) style metering device as the standard for air conditioning systems. It is now extremely important for the HVAC technician to understand the design and operation of this type of valve.

The thermostatic expansion valve (TXV) is a precision device, which is designed to regulate the rate at which liquid refrigerant flows into the evaporator. This controlled flow is necessary to maximize the efficiency of the evaporator while preventing excess liquid refrigerant from returning to the compressor (floodback).

One of the design features of the TXV is to separate the high pressure and low pressure sides of an air conditioning system. Liquid refrigerant enters the valve under high pressure via the system’s liquid line, but its pressure is reduced when the TXV limits the amount of this liquid refrigerant entering the evaporator.

Understanding the Function of the TXV

The thermostatic expansion valve controls one thing only:  the rate of flow of liquid refrigerant into the evaporator. Contrary to what you may have heard, the TXV is not designed to control:

  • Air Temperature
  • Head Pressure
  • Capacity
  • Suction Pressure
  • Humidity

Trying to use the TXV to control any of these system variables will lead to poor system performance – and possible compressor failure.

Understanding How the TXV Controls the System

As the thermostatic expansion valve regulates the rate at which liquid refrigerant flows into the evaporator, it maintains a proper supply of refrigerant by matching this flow rate against how quickly the refrigerant evaporates (boils off) in the evaporator coil. To do this, the TXV responds to two variables: the temperature of the refrigerant vapor as it leaves the evaporator (P1) and the pressure in the evaporator itself (P2). It does this by using a movable valve pin against the spring pressure (P3) to precisely control the flow of liquid refrigerant into the evaporator (P4):

TXV Pressure Balance EquationTXV
P1+P4 = P2+P3
P1 = Bulb Pressure (Opening Force)
P2 = Evaporator Pressure (Closing Force)
P3 = Superheat Spring Pressure (Closing Force)
P4 = Liquid Pressure (Opening Force)

 

Understanding How the TXV Transfers Energy

Here is a closer view of the TXV in operation. The valve pin restricts the flow of the liquid refrigerant. As the flow is restricted, several things happen:

  • The pressure on the liquid refrigerant drops
  • A small amount of the liquid refrigerant is converted to gas, in response to the drop in pressure
  • This “flash gas” represents a high degree of energy transfer, as the sensible heat of the refrigerant is converted to latent heat
  • The low-pressure liquid and vapor combination moves into the evaporator, where the rest of the liquid refrigerant “boils off” into its gaseous state as it absorbs heat from its surroundings.

The pressure drop that occurs in the thermostatic expansion valve is critical to the operation of the refrigeration system. As it moves through the evaporator, the low pressure liquid and gas combination continues to vaporize, absorbing heat from the system load. In order for the system to operate properly, the TXV must precisely control the flow of liquid refrigerant, in response to system conditions.

Share
print

Was this helpful?

Vote This Post Up 13,609Loading...

267 thoughts on “Guide to Thermostatic Expansion Valves

  1. Hi, in a much hotter more humid environment, if heat exchange on the condenser side is not optimal, I.e. ambient air is high or lacking airflow or dirty condenser, how does that affect the expansion value or the overall ac conditioner performance? Came across a product call bn6 thermal conductive coating where it improvee heat exchange on the condenser side increasing, so by having better more efficient heat exchange on the condenser side, what kind of improvement effect can I expect? Will that lead to more energy saving? Thanks

    • Hi Mike,

      Maintaining proper air flow over the outdoor coil surface is essential to achieving optimal performance. Periodically keeping the outdoor coil clean of dirt, debris, lint, trees, flowers, leaves, etc., is something we frequently include on our homeowner maintenance items.

      The charter for this site does not allow us to comment on particular products or service providers but in the general use of “coatings” for the outdoor coil it is very important to insure that the designed air flow is not reduced. Decreasing the affective heat exchange area of the outdoor coil and not removing heat from the refrigerant, greatly reduces the density (Subcooling) of the refrigerant on the outlet of the coil. TXV’s are designed so that at “wide open throttle” (full load) they expect to meter 100% liquid refrigerant through the valve body for full capacity. Any reduction in subcooling or metered liquid refrigerant would reduce the capacity of the valve and could potentially cause problems under high load system conditions, possibly resulting in compressor overheat.

      Think of the system refrigerant as a sponge, if the sponge is fully saturated with water (heat) and I don’t squeeze the sponge (condenser coil), I can’t absorb more water (heat).

      Hope this helps,
      Scott

  2. Dear Sir.
    I am engineer on cargo ship and have one question for you regarding evaporator pressure regulating valve on dairy and vegetable chamber.Have read on internet all about it and still don’t understand why the same don’t existing on meet chamber .As I have understand meat chamber evaporating pressure is the lowest and how it is possible that suction pressure on compressor is higher than outlet pressure from meet evaporating unit.If the for example pressure in dairy evaporator outlet is 6 bars,vegetable evaporator outlet 4 bars and meet evap. out 2 bars what would be the suction pressure on compresor and if it is higher than meet evap pressure how is counterpressure solved.please reply to my email adress
    Thank you for your advice
    Sasa

    • Hi Sasa,

      Typically, when you have multiple evap temps operating on the same system, you use an EPR valve to keep the pressures higher on those cases that you want to maintain at a warmer temperature. The pressure set and maintain by the EPR (at Saturation) is the temperature setting. The case that runs the coldest is the one you set the compressor suction pressure for; hence, that case does not require an EPR.

      The pressure at the evaporator outlet of the coldest case then, should be the same as the compressor suction pressure, assuming no pressure drop thru the lines. In practice, I’d expect the compressor suction pressure to be 1-2 psig LOWER than the pressure at the evap outlet…..not higher.

      It is not possible to have a lower pressure at an evaporator outlet than the suction pressure at the compressor. This would against the laws of nature, as pressure differential is needed in order have refrigerant flow in the system.

      Scott

  3. I have one free dryer (Lyophilizer)machine. This machine I’m not achieved -45°c temperature in shelf side, I have change expansion valve the model is TES2 ,-60 To -25 range,make danfoss.
    Compressor capacity is 1.5 hp , discharge pressure is 180psi. Gas:Freon R404a, expansion valve not getting ice foarmi running time when I touch expansion valve its normal temperature, I have adjust also but not find result,

    • Arun, This appears to be an application issue. You might try contacting technical support from either the OEM system provider or the (TXV) component supplier.

    • Thanks for the question. Regarding the valve type featured in this article, P4 pressure is an opening force against the valve pin due to liquid line pressure. An increase in outdoor condensing pressure effects the liquid line pressure, which influences the pressure against the valve pin seat. This results in an increase to the opening force of the valve, and is the main reason why “balanced port” TXV valves were developed. A “Balanced Port” valve looks to eliminate this P4 opening force.

      Scott

  4. In March our lennox heat pump was a block of ice. It was not defrosting. the technician told my husband to find a way to defrost it, which he did, and the tech checked it and said everything was fine. the first time this spring that we turned on the air conditioner nothing happened. The tech came and determined that we need a new TXV valve. Are these two issues related?

  5. Hi I have a doubt and i need clarifications

    I have a dehumidifier with a precooling coil capacity of 8.5TR and for this we have used 7.5TR TXV- Danfoss make . We had charged the R407c properly in the copper pipe line ( after vaccuming with the nitrogen gas ) . Compressor is running well . But we are not getting suffiicient cooling after the evaporator coil . We got 25.6deg C . It seems like things are doing good but we are not getting the req.temp..The same issues in post coil also . Kly explain .

  6. I need some help

    I have replaced TXV in an undercounter fridge with three doors, the systems is working with R507, but the txv replaced is for r 134A, the consecuence is that the fridge not reach the set point 40F, only have a fluctuation betwen 45f and 55F .
    How I can solve the problem
    thanks in advance

    • Hi Jesus,

      TXV’s are designed for operation with a specific system refrigerant as listed on the part. Many TXV’s are designed for use with a single system refrigerant, while others are designed to be interchangeable for multiple refrigerants. For example, TXV’s rated for R-507 are many times interchangeable with R-404A. In addition, TXV’s rated for R-134a are typically interchangeable with R-12. However, the TXV should be selected based upon the type of refrigerant or refrigerants listed on the part only. In this situation, the valve is likely undersized for the application and should be replaced with one specifically rated for R-507 service.

      Thanks,
      Scott

      • Thanks for the answer
        My problem is that I need to run this fridge for 20 days at list before I will get the right TXV,any tips to improve the cooling?

  7. Hey this is awesome……love the breakdown on txv operations……Been in the field a long time and still love the shop talk.

  8. Hi, Trying to diagnose my sister’s furnace problem. Electric furnace, blows air but doesn’t get hot. Does run okay in emergency heat, but expensive to operate in that mode. Wondering if the TVX should be replaced.

    • Hi Tony,

      This is a common situation that can occur during the extreme low temperatures of Winter. If a problem arises with the HeatPump unit, the furnace will produce heat by using the “back up” stage of the furnace. In your case this is the electric resistance coils in the furnace. I would recommend having a qualified HVAC Technician service the unit.

      Additional information on this topic can be found:
      http://www.ac-heatingconnect.com/zombie-heat-pumps/

      Hope this helps,

      Scott

Leave a Reply to jesus Cancel reply

Your email address will not be published. Required fields are marked *